Skip to content

Questions and answers.

What production managers, finance managers and technicians ask us first.

Production

For production and quality managers: the steam and heat must never be at risk.

Can production stop during a market activation?

BoilOptimizer only bids capacity your plant can spare, within the limits you agree with us. When the electric side steps down, the burner or your gas boiler takes over and the steam to production stays the same.

If something looks wrong, your operators take over locally. The emergency stop in the cabinet cuts all remote control while the boiler keeps running.

Does it work for hot water?

Yes. BoilOptimizer runs hot-water boilers the same way as steam boilers, and with a hot-water tank it can make heat while power is cheap and use it later. Our boilers come for steam or hot water.

Can the boiler run on both sources at full output?

Yes, if it is built for it. With larger valves, a hybrid boiler can run at full output on electricity and on the burner at the same time.

Do we need an accumulator tank?

Some processes do, to cover short peaks. It is not part of the standard delivery; if your plant needs one, we size it in the business case.

Finance

For the managing director and the CFO: what it costs, what it saves, and who carries the risk.

What can it save us?

It depends on your energy prices, your demand and the boiler you have. The calculator gives you a first range in a minute. The energy analysis gives you your own number.

What does it cost?

BoilOptimizer has a fixed monthly fee plus a share of the savings and flexibility income we document, so the fee follows the result. Our boilers can be bought or run as a service. We can also set up financing, in Norway with Enova support where your plant qualifies, so you don’t spend money before the value is clear. The energy analysis shows you the numbers first.

What if electricity costs more than gas all winter?

Then the boiler runs on gas, as it would without us, and there is little saving to share. The fixed fee is the part you always pay.

Do we need a new boiler?

No. BoilOptimizer works on existing electric, electrode, gas and oil boilers. If your boiler is near the end of its life, the Hybrid Boiler replaces it with the control built in.

Technical

For the technical manager: how the control connects, and what stays local.

How does the cabinet connect to the boiler?

Over Modbus TCP, through an industrial PC behind a firewall. The boiler’s own PLC is never exposed to the internet.

What sizes do you deliver?

From about 0.3 MW to over 10 MW per boiler, and larger plants run several boilers as one. Our boilers are sized to your site.

We get no condensate back. Does that matter?

No, but the feedwater tank is sized for it. Without condensate return, all the water comes in cold and has to be heated, so the tank must hold a full hour of output: about 3,000 litres for a boiler making 3 tonnes of steam an hour, instead of 2,000.

Is water treatment included?

Yes. A boiler from us comes with a feedwater tank, a water softener and a dosing pump, sized to your water and your condensate return.

What do we need to provide?

Access to the boiler room, your production plan and a contact person on site. We handle the market side: prequalification, bids and settlement.

Your question isn’t here?

Ask us. Boiler engineers and energy-market people answer, often in the same call.